Variable Speed Setpoint "00"® Circulator
The versatile Setpoint version of the Variable Speed “00” can
be set up to deliver a fixed temperature, maintain a specific temperature
drop between sensor locations (DT), used as a bypass/shunt pump,
or integrated into a fan coil package to vary the speed of the
pump based on supply air temperature.
The 00-VS can be either direct-acting (speed increases on a temperature
decrease) or reverse-acting (speed increases on a temperature increase).
A typical direct-acting (limiting setpoint) application would be
for boiler protection, where the 00-VS is installed on a bypass
loop. If the return temperature starts to drop below the set temperature
(75°- 165°F), then the speed of the pump will be increased, bypassing
hot water to protect the boiler. The 00-VS can be used in radiant
injection mixing systems where you want to set a fixed supply-water
temperature. Through the use of the setpoint dial on the PC board,
you can select any temperature from 30°-210°F. If desired, a boiler
protection sensor can be installed to protect the boiler from flue
gas condensation. In the DT mode, the pump speed is varied to maintain
a set temperature drop (5°-50°F) across a boiler or heat exchanger,
ideal for snowmelt applications.
FEATURES:
• Adjustable Setpoint (30° - 210°F)
• Adjustable Temperature Difference (DT) (5° - 50°F)
• Boiler Protection (135°F)
• Boiler Protection as a Limit Control (75° - 165°F)
• LED Status Panel
• Direct or Reverse Acting
• Selectable Output Response Speed
• Linear or Logarithmic Output
• Pump Exercise (10 Seconds After 3 Days of No Operation)
|